11/03 Output Terminals
SINAMICS G150
Operating Manual
8-5
Scaling
Table 8-1 Scaling
Variable Scaling parameter Default for quick commissioning
Reference speed 100 % = p2000
p2000 = Maximum speed (p1082)
Reference voltage 100 % = p2001
p2001 = 1000 V
Reference current 100 % = p2002
p2002 = Current limit (p0640)
Reference torque 100 % = p2003
p2003 = 2 x rated motor torque
Reference power 100 % = r2004
30
Ï€p2000p2003
r2004
××
=
Reference frequency
60
p2000
% 100 =
Reference control
factor
100 % = Maximum output voltage
without overload
Reference flux
100 % = Rated motor flux
Reference
temperature
100% = 100 °C
Example: Changing Analog Output 0 from Current to Voltage Output –10 to +10 V
Set analog input 0 type to -10 V ... +10 V
p4076 = 4
X522: 1,2
Voltage output present at terminal 1, ground at terminal 2
Fig: 8-2 Example: Setting analog output 0