11/03 Technical Data
SINAMICS G150
Operating Manual
12-9
Table 12-10 Version C, 380 V – 480 V, part 2
Category Unit
Order no. 6SL3710- 1GE33-8CA0 1GE35-0CA0 1GE36-1CA0
Rated motor output kW 200 250 315
Rated connection voltage V 3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
Rated input current A 405 519 639
Rated output current A 380 490 605
Base load current A 370 477 590
Power loss kW 5.3 6.4 8.2
Cooling air requirement m³/s 0.36 0.36 0.78
Sound pressure level at 50/60
Hz
dB(A) 69/73 69/73 70/73
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 120
2 x (300)
2 x 240
2 x (600)
M12 (1 hole)
2 x 185
2 x (500)
2 x 240
2 x (600)
M12 (1 hole)
2 x 240
2 x (600)
8 x 240
8 x (600)
M12 (4 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 120
2 x (300)
2 x 150
2 x (400)
M12 (1 hole)
2 x 185
2 x (500)
2 x 240
2 x (600)
M12 (1 hole)
2 x 240
2 x (600)
8 x 240
8 x (600)
M12 (4 holes)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard
version)
kg 300 300 670
Dimensions (w x h x d) mm 400 x 2000 x 600 400 x 2000 x 600 600 x 2000 x 600
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
A
3NE1 334-2
500
2
3NE1 436-2
630
3
3NE1 438-2
800
3