Technical Data 11/03
SINAMICS G150
12-12 Operating Manual
Table 12-13 Version A, 660 V – 690 V, part 2
Category Unit
Order no. 6SL3710- 1GH31-5AA0 1GH31-8AA0 1GH32-2AA0
Rated motor output kW 132 160 200
Rated connection voltage V 3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
Rated input current A 174 201 234
Rated output current A 150 175 215
Base load current A 140 171 208
Power loss kW 2.8 3.8 4.2
Cooling air requirement m³/s 0.17 0.36 0.36
Sound pressure level at 50/60
Hz
dB(A) 67/68 69/73 69/73
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
95
(4/0)
4 x 240
4 x (600)
M12 (2 holes)
120
(300)
4 x 240
4 x (600)
M12 (2 holes)
2 x 70
2 x (000)
4 x 240
4 x (600)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
95
(4/0)
2 x 150
2 x (400)
M12 (2 holes)
120
(300)
2 x 150
2 x (400)
M12 (2 holes)
2 x 70
2 x (000)
2 x 150
2 x (400)
M12 (2 holes)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard
version)
kg 320 390 390
Dimensions (w x h x d) mm 800 x 2000 x 600 800 x 2000 x 600 800 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 240-6
200
2
3NE1 225-2
200
1
3NA3 244-6
250
2
3NE1 227-2
250
1
3NA3 252-6
315
2
3NE1 230-2
315
1