11/03 Technical Data
SINAMICS G150
Operating Manual
12-13
Table 12-14 Version A, 660 V – 690 V, part 3
Category Unit
Order no. 6SL3710- 1GH32-6AA0 1GH33-3AA0 1GH34-1AA0
Rated motor output kW 250 315 400
Rated connection voltage V 3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
Rated input current A 280 353 436
Rated output current A 260 330 410
Base load current A 250 320 400
Power loss kW 5.0 6.1 8.1
Cooling air requirement m³/s 0.36 0.36 0.78
Sound pressure level at 50/60
Hz
dB(A) 69/73 69/73 72/75
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 95
2 x (4/0)
4 x 240
4 x (600)
M12 (2 holes)
2 x 120
2 x (300)
4 x 240
4 x (600)
M12 (2 holes)
2 x 185
2 x (500)
4 x 240
4 x (600)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 95
2 x (4/0)
2 x 185
2 x (500)
M12 (2 holes)
2 x 120
2 x (300)
2 x 240
2 x (600)
M12 (2 holes)
2 x 185
2 x (500)
4 x 240
4 x (600)
M12 (2 holes)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard
version)
kg 390 390 860
Dimensions (w x h x d) mm 800 x 2000 x 600 800 x 2000 x 600 1200 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 354-6
355
3
3NE1 331-2
350
2
3NA3 365-6
500
3
3NE1 334-2
500
1
3NA3 365-6
500
3
3NE1 334-2
500
1