Technical Data 11/03
SINAMICS G150
12-14 Operating Manual
Table 12-15 Version A, 660 V – 690 V, part 4
Category Unit
Order no. 6SL3710- 1GH34-7AA0 1GH35-8AA0 1GH37-4AA0
Rated motor output kW 450 560 710
Rated connection voltage V 3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
Rated input current A 493 608 774
Rated output current A 465 575 735
Base load current A 452 560 710
Power loss kW 9.1 10.8 13.5
Cooling air requirement m³/s 0.78 0.78 1.48
Sound pressure level at 50/60
Hz
dB(A) 72/75 72/75 72/75
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 185
2 x (500)
4 x 240
4 x (600)
M12 (2 holes)
2 x 240
2 x (600)
4 x 240
4 x (600)
M12 (2 holes)
3 x 185
3 x (500)
8 x 240
8 x (600)
M12 (4 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 185
2 x (500)
4 x 240
4 x (600)
M12 (2 holes)
2 x 240
2 x (600)
4 x 240
4 x (600)
M12 (2 holes)
3 x 185
3 x (500)
6 x 240
6 x (600)
M12 (3 holes)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (18 holes)
Approx. weight (standard
version)
kg 860 860 1320
Dimensions (w x h x d) mm 1200 x 2000 x 600 1200 x 2000 x 600 1600 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 352-6
2 x 315
2
3NE1 435-2
560
3
3NA3 354-6
2 x 355
3
3NE1 447-2
670
3
3NA3 365-6
2 x 500
3
3NE1 448-2
850
3