Electrical Installation 11/03
SINAMICS G150
4-22 Operating Manual
X530: 4 Digital Inputs
Table 4-9 Terminal block X530
Terminal Designation
1)
Technical data Factory Setting
1 DI 4 Command data set
selection CDS bit 0
2 DI 5 LOCAL mode disable
3 DI 6 Fixed speed setpoint
selection bit 0
4 DI 7 Fixed speed setpoint
selection bit 1
5 M2
1 2 3 4 5 6
6 M
Voltage: -3 V to 30 V
Current input (typical):
10 mA at 24 V
With electrical isolation: Reference
potential is terminal M2
High level: 15 V to 30 V
Low level: -3 V to 5 V
1)
DI: digital input; M2: ground reference; M: electronic ground
Max. connectable cross-section: 1.5 mm² (AWG 14)
NOTE
An open-circuit input is interpreted as “low“.
Terminal M1 must be connected so that the digital inputs can function correctly.
The following solutions are possible:
1) The provided ground reference of the digital inputs, or
2) A jumper to terminal M (Important: electrical isolation for the digital inputs
is revoked as a result).
X521: 2 Analog Inputs (Differential Inputs)
Table 4-10 Terminal block X521
Terminal Designation
1)
Technical data Factory Setting
1 AI 0+
2 AI 0-
Speed setpoint:
0 – 20 mA
3 AI 1+
4 AI 1-
-10 V - +10 V, R
i
= 70 kΩ
+4 mA - +20 mA
-20 mA - +20 mA, R
i
= 250 Ω
0 mA - +20 mA
5 P10 +10 V ± 1 %, I
max
5 mA
6 M Reference potential for AI 0
7 N10 -10 V ± 1 %, I
max
5 mA
87654321
8 M Reference potential for AI 1
1)
AI: analog input; P10/N10: auxiliary voltage, M: ground reference
Max. connectable cross-section: 1.5 mm² (AWG 14)
CAUTION
The input current of the analog inputs must not exceed 35 mA when current
measurements are performed.