11/03 Electrical Installation
SINAMICS G150
Operating Manual
4-23
S5: Selector for Voltage/Current AI0, AI1
Table 4-11 Selector for voltage/current S5
Switch Function Technical data
S5.0 Selector voltage/current AI0
S5.1 Selector voltage/current AI1
Voltage
S5.0
S5.1
V
I
I
V
Current
X522: 2 Analog Outputs, Temperature Sensor Connection
Table 4-12 Terminal block X522
Terminal Designation
1)
Technical data Factory Setting
1 AO 0 V+
2 AO 0 ref.
3 AO 0 A+
Actual speed value:
0 – 20 mA
4 AO 1 V+
5 AO 1 ref.
6 AO 1 A+
-10 V - +10 V
+4 mA - +20 mA
-20 mA - +20 mA
0 mA - +20 mA
Motor current actual
value:
0 – 20 mA
7 KTY+
87654321
8 KTY-
KTY84: 0...200 °C
PTC: R
PTC
≤ 1.5 kΩ
1)
AO: analog output; KTY: temperature sensor connection
Max. connectable cross-section: 1.5 mm² (AWG 14)
X540: Common Auxiliary Voltage for Digital Inputs
Table 4-13 Terminal block X540
Terminal Designation Technical data Factory Setting
1 P24
2 P24
3 P24
4 P24
5 P24
6 P24
7 P24
87654321
8 P24
24 V DC
Imax = 150 mA (total of all P24
terminals)
Max. connectable cross-section: 1.5 mm² (AWG 14)