A.9 Information List
589
7UT613/63x Manual
C53000-G1176-C160-2
188 Error Board 6 (Error Board 6) Supervision OUT ON
OFF
* * LED BO 135 176 1 Yes
189 Error Board 7 (Error Board 7) Supervision OUT ON
OFF
* * LED BO 135 177 1 Yes
190 Error Board 0 (Error Board 0) Supervision OUT ON
OFF
* * LED BO 135 210 1 Yes
191 Error: Offset (Error Offset) Supervision OUT ON
OFF
**LEDBO
191.2404 >BLOCK 3I0 time overcurrent
(>BLK 3I0 O/C)
3I0 O/C SP * * * LED BI BO
191.2411 Time Overcurrent 3I0 is OFF
(O/C 3I0 OFF)
3I0 O/C OUT ON
OFF
* * LED BO 60 151 1 Yes
191.2412 Time Overcurrent 3I0 is
BLOCKED (O/C 3I0 BLK)
3I0 O/C OUT ON
OFF
ON
OFF
* LED BO 60 152 1 Yes
191.2413 Time Overcurrent 3I0 is ACTIVE
(O/C 3I0 ACTIVE)
3I0 O/C OUT ON
OFF
* * LED BO 60 153 1 Yes
191.2425 Time Overcurrent 3I0 picked up
(O/C 3I0 PU)
3I0 O/C OUT * ON
OFF
m LED BO 60 154 2 Yes
191.2491 O/C 3I0: Not available for this
object (O/C 3I0 Not av.)
3I0 O/C OUT ON * * LED BO
191.2501 >BLOCK time overcurrent 3I0
InRush (>BLK 3I0O/C Inr)
3I0 O/C SP ON
OFF
ON
OFF
* LED BI BO 60 99 1 Yes
191.2502 >BLOCK 3I0>> time overcurrent
(>BLOCK 3I0>>)
3I0 O/C SP * * * LED BI BO 60 9 1 Yes
191.2503 >BLOCK 3I0> time overcurrent
(>BLOCK 3I0>)
3I0 O/C SP * * * LED BI BO 60 10 1 Yes
191.2504 >BLOCK 3I0p time overcurrent
(>BLOCK 3I0p)
3I0 O/C SP * * * LED BI BO 60 11 1 Yes
191.2514 3I0>> BLOCKED (3I0>>
BLOCKED)
3I0 O/C OUT ON
OFF
ON
OFF
* LED BO 60 155 1 Yes
191.2515 3I0> BLOCKED (3I0>
BLOCKED)
3I0 O/C OUT ON
OFF
ON
OFF
* LED BO 60 159 1 Yes
191.2516 3I0p BLOCKED (3I0p
BLOCKED)
3I0 O/C OUT ON
OFF
ON
OFF
* LED BO 60 163 1 Yes
191.2521 3I0>> picked up (3I0>> picked
up)
3I0 O/C OUT * ON
OFF
* LED BO 60 156 2 Yes
191.2522 3I0> picked up (3I0> picked up) 3I0 O/C OUT * ON
OFF
* LED BO 60 160 2 Yes
191.2523 3I0p picked up (3I0p picked up) 3I0 O/C OUT * ON
OFF
* LED BO 60 164 2 Yes
191.2524 3I0> InRush picked up (3I0>
InRush PU)
3I0 O/C OUT * ON
OFF
* LED BO 60 96 2 Yes
191.2525 3I0p InRush picked up (3I0p
InRush PU)
3I0 O/C OUT * ON
OFF
* LED BO 60 97 2 Yes
191.2529 3I0 InRush picked up (3I0 InRush
PU)
3I0 O/C OUT * ON
OFF
* LED BO 60 95 2 Yes
191.2541 3I0>> Time Out (3I0>> Time Out) 3I0 O/C OUT * * * LED BO 60 157 2 Yes
191.2542 3I0> Time Out (3I0> Time Out) 3I0 O/C OUT * * * LED BO 60 161 2 Yes
191.2543 3I0p Time Out (3I0p TimeOut) 3I0 O/C OUT * * * LED BO 60 165 2 Yes
191.2551 3I0>> TRIP (3I0>> TRIP) 3I0 O/C OUT * ON * LED BO 60 158 2 Yes
191.2552 3I0> TRIP (3I0> TRIP) 3I0 O/C OUT * ON * LED BO 60 162 2 Yes
191.2553 3I0p TRIP (3I0p TRIP) 3I0 O/C OUT * ON * LED BO 60 166 2 Yes
192 Error:1A/5Ajumper different from
setting (Error1A/5Awrong)
Supervision OUT ON
OFF
* * LED BO 135 169 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents

Questions and Answers: