A.9 Information List
593
7UT613/63x Manual
C53000-G1176-C160-2
207.2404 >BLOCK Phase time overcurrent
2 (>BLK Phase O/C2)
Phase O/C 2 SP * * * LED BI BO
207.2411 Time Overcurrent Phase-2 is
OFF (O/C Phase-2 OFF)
Phase O/C 2 OUT ON
OFF
**LEDBO
207.2412 Time Overcurrent Phase-2 is
BLOCKED (O/C Phase-2 BLK)
Phase O/C 2 OUT ON
OFF
ON
OFF
* LED BO
207.2413 Time Overcurrent Phase-2 is
ACTIVE (O/C Phase-2 ACT)
Phase O/C 2 OUT ON
OFF
**LEDBO
207.2422 Time Overcurrent Phase-2 L1
picked up (O/C Ph2 L1 PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2423 Time Overcurrent Phase-2 L2
picked up (O/C Ph2 L2 PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2424 Time Overcurrent Phase-2 L3
picked up (O/C Ph2 L3 PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2491 O/C Phase2 Not available for this
object (O/C Ph2 Not av.)
Phase O/C 2 OUT ON * * LED BO
207.2501 >BLOCK time overcurrent
Phase-2 InRush (>BLK
Ph.O/C2Inr)
Phase O/C 2 SP ON
OFF
ON
OFF
* LED BI BO
207.2502 >Time Overcurrent Phase-2
BLOCK I>> (>O/C2 BLOCK I>>)
Phase O/C 2 SP * * * LED BI BO
207.2503 >Time Overcurrent Phase-2
BLOCK I> (>O/C2 BLOCK I>)
Phase O/C 2 SP * * * LED BI BO
207.2504 >Time Overcurrent Phase-2
BLOCK Ip (>O/C2 BLOCK Ip)
Phase O/C 2 SP * * * LED BI BO
207.2514 Time Overcurrent Phase-2 I>>
BLOCKED (O/C Ph2 I>> BLK)
Phase O/C 2 OUT ON
OFF
ON
OFF
* LED BO
207.2515 Time Overcurrent Phase-2 I>
BLOCKED (O/C Ph2 I> BLK)
Phase O/C 2 OUT ON
OFF
ON
OFF
* LED BO
207.2516 Time Overcurrent Phase-2 Ip
BLOCKED (O/C Ph2 Ip BLK)
Phase O/C 2 OUT ON
OFF
ON
OFF
* LED BO
207.2521 Time Overcurrent Phase-2 I>>
picked up (O/C Ph2 I>> PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2522 Time Overcurrent Phase-2 I>
picked up (O/C Ph2 I> PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2523 Time Overcurrent Phase-2 Ip
picked up (O/C Ph2 Ip PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2524 Time Overcurrent Ph2 I> InRush
picked up (O/C Ph2 I> Inr)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2525 Time Overcurrent Ph2 Ip InRush
picked up (O/C Ph2 Ip Inr)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2526 Time Overcurrent Ph2 L1 InRush
picked up (Ph2L1 InRush PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2527 Time Overcurrent Ph2 L2 InRush
picked up (Ph2L2 InRush PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2528 Time Overcurrent Ph2 L3 InRush
picked up (Ph2L3 InRush PU)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2531 Time O/C Phase-2 L1 InRush de-
tected (O/C2 L1 InRush)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2532 Time O/C Phase-2 L2 InRush de-
tected (O/C2 L2 InRush)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2533 Time O/C Phase-2 L3 InRush de-
tected (O/C2 L3 InRush)
Phase O/C 2 OUT * ON
OFF
* LED BO
207.2534 Time O/C Ph-2 Cross blk: PhX
blocked PhY (O/C2 INR X-BLK)
Phase O/C 2 OUT * ON
OFF
* LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals