A.9 Information List
597
7UT613/63x Manual
C53000-G1176-C160-2
321.2501 >BLOCK time overcurrent 3I0-2
InRush (>BLK 3I0O/C2Inr)
3I0 O/C 2 SP ON
OFF
ON
OFF
* LED BI BO
321.2502 >BLOCK 3I0>> time overcurrent
2 (>BLOCK 3I0-2>>)
3I0 O/C 2 SP * * * LED BI BO
321.2503 >BLOCK 3I0> time overcurrent 2
(>BLOCK 3I0-2>)
3I0 O/C 2 SP * * * LED BI BO
321.2504 >BLOCK 3I0p time overcurrent 2
(>BLOCK 3I0-2p)
3I0 O/C 2 SP * * * LED BI BO
321.2514 Time Overcurrent 3I0-2 3I0>>
BLOCKED (3I0-2>> BLOCKED)
3I0 O/C 2 OUT ON
OFF
ON
OFF
* LED BO
321.2515 Time Overcurrent 3I0-2 3I0>
BLOCKED (3I0-2> BLOCKED)
3I0 O/C 2 OUT ON
OFF
ON
OFF
* LED BO
321.2516 Time Overcurrent 3I0-2 3I0p
BLOCKED (3I0-2p BLOCKED)
3I0 O/C 2 OUT ON
OFF
ON
OFF
* LED BO
321.2521 Time Overcurrent 3I0-2 3I0>>
picked up (O/C 3I0-2>> PU)
3I0 O/C 2 OUT * ON
OFF
* LED BO
321.2522 Time Overcurrent 3I0-2 3I0>
picked up (O/C 3I0-2> PU)
3I0 O/C 2 OUT * ON
OFF
* LED BO
321.2523 Time Overcurrent 3I0-2 3I0p
picked up (O/C 3I0-2p PU)
3I0 O/C 2 OUT * ON
OFF
* LED BO
321.2524 Time O/C 3I0-2 3I0> InRush
picked up (3I0-2>InRush PU)
3I0 O/C 2 OUT * ON
OFF
* LED BO
321.2525 Time O/C 3I0-2 3I0p InRush
picked up (3I0-2p InRushPU)
3I0 O/C 2 OUT * ON
OFF
* LED BO
321.2529 Time Overcurrent 3I0-2 InRush
picked up (3I0-2 InRush PU)
3I0 O/C 2 OUT * ON
OFF
* LED BO
321.2541 Time Overcurrent 3I0-2 3I0>>
Time Out (3I0-2>>Time Out)
3I0 O/C 2 OUT * * * LED BO
321.2542 Time Overcurrent 3I0-2 3I0>
Time Out (3I0-2> Time Out)
3I0 O/C 2 OUT * * * LED BO
321.2543 Time Overcurrent 3I0-2 3I0p
Time Out (3I0-2p Time Out)
3I0 O/C 2 OUT * * * LED BO
321.2551 Time Overcurrent 3I0-2 3I0>>
TRIP (O/C 3I0-2>>TRIP)
3I0 O/C 2 OUT * ON * LED BO
321.2552 Time Overcurrent 3I0-2 3I0>
TRIP (O/C 3I0-2> TRIP)
3I0 O/C 2 OUT * ON * LED BO
321.2553 Time Overcurrent 3I0-2 3I0p
TRIP (O/C 3I0-2p TRIP)
3I0 O/C 2 OUT * ON * LED BO
322 Warn: Limit of Memory Operation
exceeded (Warn Mem. Oper.)
Device OUT ON
OFF
**LEDBO
322.2413 Dynamic settings O/C 3I0-2 are
ACTIVE (3I0-2 Dyn.s.ACT)
ColdLoadPickup OUT ON
OFF
ON
OFF
* LED BO
323 Warn: Limit of Memory New ex-
ceeded (Warn Mem. New)
Device OUT ON
OFF
**LEDBO
323.2404 >BLOCK 3I0 time overcurrent 3
(>BLK 3I0 O/C 3)
3I0 O/C 3 SP * * * LED BI BO
323.2411 Time Overcurrent 3I0-3 is OFF
(O/C 3I0-3 OFF)
3I0 O/C 3 OUT ON
OFF
**LEDBO
323.2412 Time Overcurrent 3I0-3 is
BLOCKED (O/C 3I0-3 BLK)
3I0 O/C 3 OUT ON
OFF
ON
OFF
* LED BO
323.2413 Time Overcurrent 3I0-3 is
ACTIVE (O/C 3I0-3 ACT)
3I0 O/C 3 OUT ON
OFF
**LEDBO
323.2425 Time Overcurrent 3I0-3 picked up
(O/C 3I0-3 PU)
3I0 O/C 3 OUT * ON
OFF
* LED BO
323.2491 O/C 3I0-3: Not available for this
object (O/C 3I0-3 n/a)
3I0 O/C 3 OUT ON * * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation