6.8 Connecting the fuse module (option)
SIRIUS 3RM1 motor starter
124 Manual, 06/2016, A5E0345285095020A/RS-AE/005
6.8
Connecting the fuse module (option)
DANGER
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
Requirements
Make sure the rated operational current of the fuses fitted in the module is less than 25 A.
Procedure
Step
Description
Figure
1 Connect the infeed end of the cables marked L1 to
L3 at the 3RM1 motor starter using the connection
system provided. For further information, see the
following chapters:
"Connecting the screw-type terminals (Page 111)"
"Connecting the push-in terminals (Page 114)"