Description
3.6 Accessories and article number scheme
SIRIUS 3RM1 motor starter
48 Manual, 06/2016, A5E0345285095020A/RS-AE/005
3.6.2
Accessories
The following accessories are offered for the 3RM1 motor starter:
Infeed system (Page 48)
Fuse module (Page 49)
Sealable cover (Page 51)
Wall mounting (Page 51)
Device connectors (Page 52)
Terminals (Page 55)
Device identification label (Page 55)
3.6.2.1
Infeed system
The infeed system comprises 3-phase busbars, one infeed terminal, and one protective cap
for covering unused connections. The infeed system is suitable for 3RM1 motor starters with
screw connections.
Time-saving wiring between 3RM1 motor starters with screw terminals to the supply
connection is possible thanks to the infeed system with 3-phase busbars.
These busbars are available in three lengths, thus allowing 2, 3 or 5 motor starters (arranged
side-by-side) to be connected at the same time. More than 5 devices can be connected by
clamping the connection tags of an additional busbar rotated by 180° (e.g. 6 devices using
one 5-pole busbar and one 2-pole busbar).
A single motor starter can be removed from the assembly without loosening the terminal
screws of neighboring motor starters.
The maximum summation current must not exceed 25 A (UL: 16 A). Primary infeed is
connected via a three-phase infeed terminal. The three-phase busbars are finger-safe but
empty connection tags must be fitted with covers.