EasyManua.ls Logo

Siemens SIRIUS 3RM1 - Alarms, Faults and System Events; Leds; Status Indicators of the 3 RM1 Motor Starter

Siemens SIRIUS 3RM1
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operator control and monitoring
7.2 Displays and location of the connections
SIRIUS 3RM1 motor starter
Manual, 06/2016, A5E0345285095020A/RS-AE/005
131
7.2.1
Alarms, faults and system events
7.2.1.1
LEDs
The 3RM1 motor starter provides device status information via four LEDs:
LED
Displayable colors
DEVICE
Red/green/yellow
FAILURE
Red
STATE
Green
RESET MODE Green
7.2.1.2
Status indicators of the 3RM1 motor starter
The 3RM1 motor starter indicates the status messages for operation, fault and test via the
LEDs:
Operation
LED
Fault
signaling
output
Reaction of
feedback
circuit
Device status / operating mode
DEVICE
FAILURE
STATE
RESET
MODE
Green Off Off Green/off* - -
Control supply voltage (A1, A2) present;
Motor off;
No fault
Green Off Green Green/off* - -
Motor on;
No fault
X
X
X
Green
-
-
RESET MODE: Automatic
X
X
X
Off
-
-
RESET MODE: Manual
X = LED status not relevant; * = depending on the selected RESET MODE