Glossary   
 
  SIRIUS 3RM1 motor starter 
192  Manual, 06/2016, A5E0345285095020A/RS-AE/005 
The trip class of an inverse time-delay overload relay specifies the maximum tripping time 
from cold at a particular load. The trip class number (e.g. CLASS 10A) represents the 
maximum permissible tripping time in seconds when the 3RM1 motor starter is subjected to 
a symmetrical 3-pole load from cold with 7.2 times the current setting (IEC 60947-4-1; 
DIN VDE 0660 Part 107).  
The tripping characteristic (curve) is the graphical representation of the relationship between 
the tripping time and the influencing variable. The time/current diagram can be used to find 
out, for example, how long it will take for the release or the tripping relay to operate at a 
particular current. 
Tripping current (of an overload release) 
The current value at which a release trips within a certain time. 
The load feeder may be non-operational after a short circuit has been cleared. Damage to 
the 3RM1 motor starter is permissible.  
The 3RM1 motor starter remains functional after a short-circuit. 
The IEC 60947-4-1 (VDE 0660 Part 102) standard distinguishes between two types of 
coordination (type of coordination) referred to as coordination type "1" and coordination type 
"2". The short circuit that needs to be dealt with is cleared reliably and safely with both types 
of coordination; the only differences are in the extent of the damage sustained by the device 
following a short circuit. 
According to IEC 60947-4-1, the application area of and the load applied to 3RM1 motor 
starters can be identified by looking at the specified utilization category in conjunction with 
the specified rated operational current or the motor power and the rated voltage. An example 
is utilization category AC 53 a for starting and switching off squirrel-cage motors.