3.5 Functions
SIRIUS 3RM1 motor starter
Manual, 06/2016, A5E0345285095020A/RS-AE/005
41
ATEX-specific safety data
The motor protection function according to ATEX in the case of 3RM11/3RM13 motor
starters has the following safety data:
Safety integrity level (SILCL)
2
Hardware fault tolerance (HFT)
0
Interval for testing the protective functions
3 years
Probability of failure on demand (PFD)
5x10
-4
Probability of a dangerous failure per hour (PFH) 5x10
-8
1/h
Note
See the data sheet for other specifications. You will find the data sheet in Service&Support
(
https://support.industry.siemens.com/cs/ww/en/ps/16311/td).
Maintenance and repairs
These devices are maintenance-free.
Note
Repairs to the device may only be carried out by the manufacturer.
Warranty
NOTICE
To meet the conditions of the warranty, you must observe the safety and commissioning
instructions.