Mounting
7.3 Assembly and disassembly with different mounting systems
SIRIUS - SIRIUS 3RA load feeders
Manual, 09/2016, A5E03656507520A/RS-AB/003
85
Place the motor starter protector on the DIN rail adapter.
Screw the motor starter protector on the DIN rail adapter. The motor starter protector sits tight
on the adapter.
Tightening torque: 1.5 ... 1.6 Nm
Insert the connectors on the link module (U
i
= 690 V), as shown in the figure, into the bottom
main conductor terminals on the motor starter protector.
Screw the main conductor terminals tight.
Slide the contactor onto the link module from below. Insert the connectors on the link module
into the top main conductor terminals on the contactor.
Screw the contactor to the DIN rail adapter. The contactor sits tight on the adapter.
Tightening torque: 1.5 ... 1.6 Nm
Screw the main conductor terminals of the contactor tight.