Mounting
7.3 Assembly and disassembly with different mounting systems
SIRIUS - SIRIUS 3RA load feeders
Manual, 09/2016, A5E03656507520A/RS-AB/003
87
Place the motor starter protector on the DIN rail adapter.
Screw the motor starter protector on the DIN rail adapter. The motor starter protector sits tight
on the adapter.
Tightening torque: 1.5 ... 1.6 Nm
Place the connectors on the link module (U
i
= 690 V), as shown in the figure, into the top main
conductor terminals on the contactor.
Screw the main conductor terminals tight on the contactor.
Place the reversing contactor assembly with the fitted link module onto the DIN rail adapter and
guide the reversing contactor assembly onto the motor starter protector from below. Insert the
connectors on the link module into the bottom main conductor terminals on the motor starter
protector.
Screw the reversing contactor assembly to the DIN rail adapter. The reversing contactor
assembly sits tight on the adapter.
Tightening torque: 1.5 ... 1.6 Nm
Screw the main conductor terminals of the motor starter protector tight.
Attach the wiring modules for connecting the main current paths to the contactors from below.
Disassembling the feeder from the DIN rail adapter
To disassemble the feeder, unscrew the screws and pull the feeder down to remove it.

Table of Contents

Other manuals for Siemens SIRIUS 3RV1.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS 3RV1.2 and is the answer not in the manual?

Siemens SIRIUS 3RV1.2 Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS 3RV1.2
CategoryRelays
LanguageEnglish

Related product manuals