Transmitter MAG 8000Standard
(7ME6810)
MAG 8000 Irrigation
(7ME6880)
MAG 8000 CT
(7ME6820)
Flow unit Europe std. Volume: m
3
Flow rate: m
3
/h
US std. Volume: Gallon
Flow rate: GPM
Australia std. Volume: ML
Flow rate: ML/d
Other selecta‐
ble units
Volume:
m
3
x 100, L x 100, G x 100,
G x 1000, MG,
CF x 100, CF x 1000, AF, Al,
kL, BBL42
Flow rate:
m
3
/min, m
3
/h, m
3
/d, L/s, L/
min, L/h, ML/d, GPS, GPH,
GPD, MGD, GPM, CFS,
CFM, CFH, BBL42/s, BBL42/
min, BBL42/h, BBL42/d
Volume:
m
3
x 100, L x 100, G x 100, G x 1000, MG,
CF x 100, CF x 1000, AF, Al, kL
Flow rate:
m
3
/min, m
3
/h, m
3
/d, L/s, L/min, L/h, ML/d, GPS, GPH, GPD,
MGD, GPM, CFS, CFM, CFH
Other units than m
3
and m
3
/h (ordered from factory or manually configured onsite by chang‐
ing scaling factors) are shown by a label stuck onto display
Digital output Nos. 2 passive outputs (MOS), individually galvanically isolated
Load Max. ± 35 V DC, 50 mA short circuit protected
Output A Programmable as:
Pulse volume, Forward, Reverse, Forward/net, Reverse/net
Output B Programmable as:
Pulse volume, Forward, Reverse, Forward/net, Reverse/net , Alarm, Call-up
Pulse rate Basic version: Max. 50 Hz
Advanced version: Max. 100 Hz
Pulse width 5, 10, 50, 100, 500 ms
Communica‐
tion
IrDA Standard integrated infrared communication interface with MODBUS RTU protocol
Add-on mod‐
ules
RS 232 serial interface with MODBUS RTU (Rx/Tx/GND),
point to point with max. 15 m cable
RS 485 serial interface with MODBUS RTU (+/-/GND),
multidrop with up to 32 devices with max. 1000 m cable
Encoder interface module (for Itron 200WP) "Sensus protocol"
GSM/GPRS module with or without analog input cable
*: Only MAG 8000 Irrigation (7ME6880)
10.4 Power supply
Power supply
Battery power supply
1)
Internal battery pack 1 D-Cell 3.6 V / 16 Ah
Internal battery pack 2 D-Cell 3.6 V / 33 Ah
External battery pack 4 D-Cell 3.6 V / 66 Ah
Technical data
10.4 Power supply
SITRANS MAG 8000
94 Operating Instructions, 11/2018, A5E03071515-AE