C.2.8 800-899
Param‐
eter ID
Meter
version
Display
view
Parameter/data type Factory settings Data range
Fixed parameter or meter data that are not changeable
800 Advanced - Insulation test enable No Yes / No
Value is reset to "No" when up‐
loading device parameters to pc
after 4 minutes
801 Advanced - Insulation test interval 30 0 to 65535
802 Advanced - Insulation value
803 Advanced - Insulation test date 2000-01-01 T00:00 year-month- day T hours:mi‐
nutes:seconds
804 Advanced - Insulation tests fulfilled 0
810 Advanced - Leakage detection mode Off Off / fixed limit / lowest + fixed
limit
811 Advanced - Leakage source Flow rate Flow rate / volume
812 Advanced - Start period for leakage
detection
120 min = 2:00 [24:00] 0 to 1440 detection minutes (0
to 23:50)
813 Advanced - Duration leakage detec‐
tion
0 0 to 144 (10 to 1440 minutes)
814 Advanced - Leakage value unit Flow / volume unit The unit is updated once param‐
eter 811 change is downloaded
to the device and afterwards up‐
loaded to the pc
815 Advanced - Leakage limit 1 0 to 1x10
9
The unit is updated once param‐
eter 811 change is downloaded
to device and afterwards uploa‐
ded to pc
816 Advanced - - Leakage excitation fre‐
quency
1.5625 Hz 1/60 Hz, 1/30 Hz, 1/15 Hz,
1/5 Hz, 1.5625 Hz, 3.125 Hz,
6.25 Hz
Appendix
C.2 Parameter lists
SITRANS MAG 8000
152 Operating Instructions, 11/2018, A5E03071515-AE