5.4 Outputs
Pulse output connection diagram for MAG 8000
MAG 8000 internal connection
①
②
③
Output A
Output B
Passive output - no polarization - open drain
External connection variant
④
⑤
⑥
Positive pule logic
Negative pulse logic
Signal
Pulse output can be configured as volume, alarm or call-up, see Commissioning (Page 53).
Pulse output is not polarized and can be connected for positive or negative logic.
Pull up/down resistor (R) is selected in relation to power supply voltage (V) and with a max.
current (I) of 50 mA.
Note
Pulse output isolation
The MAG 8000 pulse output has a functional isolation only and must therefore be connected
to equipment complying with the Low Voltage Directive in order to be considered safe.
Connecting
5.4 Outputs
SITRANS MAG 8000
36 Operating Instructions, 11/2018, A5E03071515-AE