1.5 Summary of technical data FC330A-x (4 loops)
Processing capacity
− Addressable Synova® detectors (SynoLOOP)
optional (K3M030)
2 loops each with max. 128 addr. devices or
2 stub lines each with max. 32 addr. devices
+ 2 loops each with max. 128 addr. devices or
+ 2 stub lines each with max. 32 addr. devices
− Conventional detectors optional (K3M010/020) 4 or 12 lines with max. 32 conventional detectors
– Audible alarm devices
optional (K3M010)
optional (K3G050)
2 monitored control lines max. 0,5A/24VDC
+2
+2
– Alarm contacts
optional (K3M010)
2 ratings max. 1A/30VDC
+2
– Programmable driver outputs
optional (K3M010/020)
optional (K3G050)
8 ratings max. 48mA/24VDC
+ 4 or +8
+4
– Programmable contact outputs optional (K3G050)
optional (K3G060)
optional (K3I110)
8 ratings max. 1A/30VDC
8x(2x48) external
16 external, ratings max. 1A/30V
DC
– Remote transmission outputs 2 monitored control lines max. 0,5A/24VDC
2 contacts ratinged at max. 1A/30VDC
– Text indicating panel optional (B3Q580)
– Text control panel optional (B3Q59x)
– LED indicating panel optional (B3R080)
optional (B3R051)
...16 LCD
...16 LCD
1 internal
8x2 external
– LED driver outputs optional (K3L100)
optional (K3R072)
32 internal
8x(2x48) external
– Programmable control inputs
optional (K3I110)
4
16 external, only for detector zones
Power supply
mains side:
− operating voltage
− power consumption
115/230VAC "15% (VdS: +10%) 50...60Hz
max. 100VA
low voltage side:
− system supply voltage
− max. current power supply
− built in emergency power battery
u 21,5 ...v 29,5V (temperature compensated)
limited at 2,5A
2 x 12V max. 17/24Ah
− total current available for all control and 24V outputs
− battery charger
− battery load test
− battery operation upon mains power failure
− battery low discharge cut off
1.5A (with Z3I1020 max. 1A)
lead acid / 2 x 12V max. 17/24Ah, see page 21, 22
manually via operating menu / automatically 1 x per 24h
72h, see page 106
v 21,8V
Optional power supply (Z3I1000)
mains side:
− operating voltage
− power consumption
115/230VAC "14% / –20% 50...60Hz
max. 120VA
low voltage side:
− system supply voltage
− max. current power supply
29,6VDC +/–2%
limited at 3,5A
Ambient conditions
Temperature operation
storage
0°C ... +50°C (VdS: +...40°C)
−20°C ... +60°C
Humidity
max. 95%, no condensation
according to IEC721-3-3 class 3K5
IP protection category (EN60529 / IEC529) IP40
Standard EN 54-2: 1997
EN 54-4: 1997 / A1: 2002
EN 50130-4: 1995 + A1: 1998 + A2: 2003
EN 60950-1: 2001
EN 61000-6-3: 2001
Dimensions
FC330A-1/-2/-2-CH/-5/-6
FC330A-4
W = 580mm H = 480mm D = 120mm
W = 510mm H = 540mm D = 200mm
Weight
FC330A-1/-2/-2-CH/-5/-6
FC330A-4
approx. 11,5 kg without battery and optional modules
approx. 20,5 kg ” ” ”
Colour
− Control unit
− Operating panel (keyboard membrane)
RAL7035 light grey
Pantone 421C grey, 424C dark grey
Programming on site with built-in operating panel or PC configuration tool