2.15 Connecting SynoLOOP devices
Note:for technical details see page 109
−> list order and type of all devices (field device list)
+
++
AI340
micro terminals
AI300
−+−+−+
Response
indicator
AI340
max. 2 response indicators
L L
+
MT320A
EOL22(Ex)
collective
line
1234
GH
GHQRVW
QRVW
Z
LM CO NN LM
CO NC NO Z Z Z
L
L
front end
+
DFB1190
24VDC
Smoke/heat detectors
Flame detectors
Manual call points
In-/and output module
EOL1
control
line
or
ABI322A
APMK=2
30V/1A
30V/1A
4k75
4k75
free terminals
Output module
AB322A
APMK=2
Input module
EB322A
APMK=1
APMK=1
APMK=5
Base SO320A
OP320A
HI320A/322A
OH320A
APMK=1
DF1191/92
In-/or output module
CB320A or DC1192
APMK=3
+
+ +
+ +
+ + +
+ + +++
–> set to ’SynoLOOP’
–> set to
’SynoLOOP’
Note:
Always both
in-/and output
must be used
−+−++
MT320A
CB320A or DC1192
ABI322A
AB322AEB322A
−+−++
Base SO320A
−+−
rear end
+
SynoLOOP allows max. 128 devices
(cable max. 150W / 300nF)
Loading capacity: addition of loading factor of all devices (APMK=...) shall not exceed the value of 128
details see page 110
details see page 111
1)
1)
1)
1) max. 64 output
modules per
system FC330A
application with explosion
hazard area see page 34
*
DM1133A
OP620A
HI62xA
OH620A
Sockel SO620A
DM1133A