6.3 SynoLOOP
Function Features / Characteristics
Max. number of devices per line ...128 per loop
....32 per stub line
....64 addressable output modules per system FC330A
Connectable line device types serie SynoLINE300/600
OP320A/620A smoke detectors
OH320A/620A multi sensor detectors
HI32xA/62xA heat detectors
DF1191/92 flame detector
MT320A/DM1133 manual call points
CB320A/DC1192 in-/output devices
EB/AB/ABI322A in-/output devices
Details see manual
FD-M or overview
on page 32
Loading factor line devices have an individual loading factor
(depending on device type see page 32)
Detector with external alarm indicator (AI) − max. 2 AI3xx admissible per detector (device)
− max. output current 15mA
− flash interval: active phase 32ms / inactive phase 1sec
Line type − 1 loop + 1 stub line or 2/4 loops or 2/4 stub lines
− programmable via user functions
Communication principle sensor / actor-bus
− Cerberus protocol ’K1131’, serial communication
− typical 14 bit (2 priority / 8 address-bits / 4... data-bits)
− start-up addressing mode as ’daisy-chain’
Polling principle cyclical polling with alarm interrupt (alarm interrupt only MT3xx / ABI32xA)
Polling sequence during state ’quiescent’:
response upon alarm:
polling of 1 device per 0,5 sec.
(with 128 devices = each device is polled every 64 sec.)
within 2 sec. (by means of ’alarm interrupt’)
Information from detector to FC330A state ’quiescent’
’call point alarm’
’alarm-HS’ (increased sensitivity)
’alarm-LS’ (normal sensitivity)
’fault’
’drift’
Information from FC330A to detector − activation ’alarm indicator’ inside detector, call point, etc.
− activation output contact AB.../ABI... or control line on CB320A
Allocation line device logical ZONE
special feature:
according to ’order of installation’
Default allocation: device 1 line 1 ZONE 1
device 1 line 2 ZONE 129 etc.
Line break detection detected by missing device(s) in mode ’stub line’ or
detected by EOL circuit (inside FC330A) in mode ’loop-line’
Loop supervision detected by missing device(s) or by periodical supervising session
of the return line (sequence every 55 sec)
Line short circuit detection
short circuit ( 130) initiates a ’line start-up’ in order to locate and
isolate the faulty section within the line
short circuit (130....1000) initiates the isolation of the faulty section
within the line
each device has a built in line separator
Installation line cable type:
line resistance:
line capacitance:
twin wire, twisted, non-shielded
(use of existing untwisted cable is admissible)
max. 150
max. 300nF
Line specification voltage during ’polling phase’: 10V
voltage during ’charging phase’: 24V
max. current (limited): 100mA
Device specification
max. current consumption (quiescent): 200A (310A control unit side)
internal resistance ’during start-up’: 
designed as sensor/actor (non-latching)