6.7 Remote transmission outputs (RT)
Pluggable terminal block K5
Remote transmission
ALARM (fire brigade)
1
2
3
4
+
−
NO
C
5
6
7
8
NC
+
−
NO
9
10
C
NC
F7
0,5A/F
F8
0,5A/F
Remote transmission
FAULT (fire brigade)
24V
max. 30V / 1A
max. 30V / 1A
24V
external
remote transmission
equipment
max. 0,5A
max. 0,5A
FIRE/FAULT
max. 0,5A
Pluggable terminal block K5
Remote transmission
ALARM (fire brigade)
1
2
3
4
+
−
NO
C
5
6
7
8
NC
+
−
NO
9
10
C
NC
Remote transmission
FAULT (fire brigade)
max. 30V / 1A
max. 30V / 1A
FIRE/FAULT
FC330A (K3X020)
FC330A (K3X030)
internal remote
transmission
equipment
internal remote
transmission
equipment
Characteristics
For initiation of remote transmission device, either via contact or monitored control line
”Remote alarm/Remote fault” control lines
Designed for signal receiver (24VDC) with relay and series diode
Line active for ”Remote alarm” or ”Remote fault”
can also be used for flashing beacons
Line monitored by termination resistor 3,01k ½W (1%)
Operating functions for ”remote transmission alarm” (via menu)
− ON/OFF switching
− Activation (test)
Programmable functions for ”remote transmission alarm”
− Detector zone (alarm) from which the RT-alarm and the contact is to be activated
− Active phase of RT-fault until ”acknowledged” or until ”reset”
Technical data
Contact rating max. 1A/30VDC
Nominal voltage in normal operation (line monitoring) 11..12V
Nominal voltage in active phase (alarm) 24....29VDC (reversed polarity)
Max. current in active phase 500mA
Line termination
resistor 3,01k ½W (1%)