Loading...
Fire Safety & Security Products
Building Technologies
1583_o_en_−−_5
70
08.2005
5.5 Data transfer control unit <−> SWE330A
Proceed as shown below.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
FUNCTIONS: 1. function
(4) 2. system TEST
3. printout
4. configuration
CONFIGURATION: 1. user functions
(4.4) 2. user text
3. service functions
4. erase functions
Press «
Start/stop
» key and enter the password
(0055 ok)
and proceed as follows
(Code 8642 ok )
SERVICE LEVEL: system configuration
> password?
hm: back to menu Stop: end operating
CONFIGURATION: 1. system data
(4.4.1) 2. collective line
3. password
4. addressable line
5. SWE330A
6. LON devices
7. serial ports
8. K6 inputs
enter 5 or select ’5.’ with arrow key
SWE TOOL active on port: ###### 1. NO
Select? 2. YES
option ’2.’ YES = ready to communicate with SWE
enter ’2.’ to set control unit to mode data transfer
enter ’1.’ after data transfer is completed (timeout ...min
.)
The connection is established if state ’connected....’ is indicated on the PC (SWE330A). Proceed by open
menu ’file’ and selecting either ’Export’ or ’Import’.