EasyManua.ls Logo

Siemens Synova FC330A - Mounting of Optional Power Supply Z3 I1000 to FC330 A-X (4 Loops)

Siemens Synova FC330A
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fire Safety & Security Products
Building Technologies
1583_o_en_−−_2
30
08.2005
2.13 Mounting of optional power supply Z3I1000 to FC330A-x (4 loops)
Z3I1000 not possible with cabinet series ’Nordic’ from product status > 05
Assembly set, suitable to be added onsite, consisting of:
AC/DC Converter B2F040
Support plate for converter B2F040
Monitoring card M3P140
connect see page 31
Monitoring card M3P140
160"0,5
53
60
support plate
2 Pan head screws M3x8
Converter B2F040
2 Pan head
screws M3x4
Mains terminals
E
N
L1
Dismantling B2F040 to change AC input voltage to 115VAC
A
A
115V
230V
FS1
L
Protection for
mains cable
Terminals ’L/N/G’ power
supply connection
Mounting hole
Terminals
’−/+’ load 24V
Mounting screw and
stud for metal cover
Jumper for
switchover 115V
AC / 230VAC
Mains fuse ’FS1’ 3A
Mounting hole
Note:
Check mains voltage setting before commissioning
The converter is set to 230V
AC at the factory
To switch over to 115V
AC remove metal cover (remove screw
and stud) and then change jumper to pin ”115V
AC
DANGER