Fire Safety & Security Products
Building Technologies
1583_o_en_−−_2
31
08.2005
2.14 Connecting optional power supply set Z3I1000 to FC330A-x (4 loops)
mounting see page 30
to converter B2F040
red
blue
red
blue
to batteries
to K3X020
K6
K8
Fuse ’F1’: 3,15A/T
supply output
Fuse ’F2’: 3,15A/T
supply output
LED ’H1’ green: DC/converter on
LED ’H2’ green: DC/battery on
LED ’H3’ green: DC/output on
To provide additional power to peripheral devices
Output rating max. 3,5A/29,6VDC
Also backed up on internal battery
External load must also be included in capacity balance
can only be used with internal battery
Output voltage
29.6V
DC / max. 3.5A
Supply input
24V / converter
3A
Input voltage (115VAC)
230V
AC / 50...60Hz
max. 120VA
Ground
Neutral
Note:
Converter B2F040 may only be built into
cabinets which are not accessible to un-
authorized persons (Safety regulations)
B2F040
G
N
L
COM
COM
+V
+V
−
−
FS1
Phase
M3P140
2
1
external load
2
1
F2
+
–
+
–
K1
Supply input
24V / battery
K2
F1
3,15A/T
Monitoring
2
1
–
+
K3
Supply output
24V / max.3A
2
1
–
+
K4
Pluggable terminal block K8
Pluggable terminal block K6
1
−
1
2
3
4
+
+
+
−
5
6
−
−
F1
1A/F
F2
0,5A/F
Supply output
24V
DC
INPUT 0
Programmable control input
+24V
0V
MAX. 1
Terminals K9
Battery
Charging / monitoring
F3
2
1
+
−
3,15A/T
2 x 12V/12Ah
F4
BATTER
Terminals AC
Mains
F9
3
2
1
4
F10
0,8AT
0,8AT
mains 230VAC
ground connection door
K3X020
black
black
red
blue
blue
red
DANGER
E
N
L1