7 Trouble shooting
7.1 Interpretation of fault messages
1) If such error messages occur frequently then report the exact wording of the message to the hotline
Display shows
Cause / Action to be taken
24V supply too low
Battery voltage is too low and mains disconnected.
restore mains voltage then reset
24V supply too high
Battery voltage is too high.
check mains voltage if ok % replace K3X...
battery capacity INSUFFICIENT
Negative result of ’battery load test’ (voltage 23.5V with load of
0.7..1A for 10sec’ not
achieved).
replace battery then reset
BREAK > line ##
Break in detector loop.
check cable connection
BREAK in coll. line ##/zn ###
Break in conventional line, missing detector or EOL20.
check detector base and wiring
BREAK in line to FSD / key missing
Wire break in line to FSD (only with VdS card).
check wiring
BREAK in line to HM/UE
Wire break in line to ÜE.
check wiring
BREAK in spec. zone ### (coll.ln) Break in conventional line with 1min fault delay.
check detector and installation
Broken glass on coll.ln, zone ###
Broken glass on a manual call point.
replace broken glass then reset
ConTrol zn ###/##: dev. DEFECTIVE
Displayed device is defective or if device is CB320A or
DC1192 possibly without 24V supply.
replace or check device
ConTrol zn ###/##: needs CONFIG.
Devices have been removed and new devices have been in-
serted.
assign device to zone
ConTrol zn ###/##: NO RESPONSE
Displayed device (AB... or ABI... or CB...) is missing.
check device or wiring
ConTrol zn ###/##: UNKNOWN state
Displayed device (AB... or ABI... or CB...) is defective.
check device
Door OPEN on FSD
Door open at FSD after fire alarm is reset (only with VdS
card).
check FSD device
EARTH FAULT to 0V
Resistance to earth of potential ‘24V’ <17k Ω, also onboard–
LED ’LD1’ lit.
remove all pluggable terminals until fault disappears, then
repair the defective wiring
EARTH FAULT to 24V
Resistance to earth of potential ‘24V’ <17k Ω, also onboard–
LED ’LD1’ lit.
remove all pluggable terminals until fault disappears, then
repair the defective wiring
EARTH FAULT on LON device ##
Earth fault on corresponding LON-device.
restore short to earth or remove jumper ’X30’ on K3I110
Error:Buffer empty, Mess. ###, Timer ###
Indicates a software problem. 1)
unpower system and re−power again
(if message comes on again replace main board K3X...)