Error:Checksum fault in area: ###
Indicates a hardware problem. 1)
unpower system and re−power again
(if message comes on again replace main board K3X...)
Error:Mod.###,Id.##,Par1.#### Par2.####
Indicates a software problem. 1)
unpower system and re−power again
(if message comes on again replace main board K3X...)
Error:Code execution error, Flag ###
Indicates a software problem. 1)
unpower system and re−power again
(if message comes on again replace main board K3X...)
External FAULT
External fault input activated.
check connected devices
Ext. Fault: Mains power
Ext. Fault: Battery
Ext. Fault: power supply
External fault mains power, battery, power supply.
check device connected to ’K6’ (Z3I1000 etc.)
External power supply fault
Fault on power supply input ’K50’.
check input ’K50’ on K3X...
EXTINGUISH device activation FAULT
Message ’extinguishing actuated’ without command
from fire alarm panel (only with VdS card).
check extinguishing device
FAULT in line to EXTINGUISH device
Open or short circuit in line to extinguishing device.
check wiring
Fault on BMS−communication
Communication fault on BMS communication.
check connection from PC to control panel
FAULT port RS232
Communication problem in serial ports.
reset (if fault does not disappear, or if this is taking place
frequently replace K3X...)
FAULT: re−alarm coll.ln, zone ###
Zone is re−alarmed immediately (< 20sec) after reset.
(possibly defective detector).
locate alarming detector check situation
FSD: door manually opened
FSD is released manually by switch ’S1’ on VdS card K3L070
or unauthorized manipulation.
check VdS card
fuse ’battery’ BLOWN
Battery disconnected or fuse F3/F4 blown possibly due to
wrong polarity.
⇒ check battery and/or replace fuse then reset
fuse ’supply outp. 24V/0.5A’ BLOWN
On power output 24V fuse ’F2’ blown.
check connected load and replace fuse
fuse ’supply outp. 24V/1A’ BLOWN
On power output 24V fuse ’F1’ blown.
check connected load and replace fuse
HM/UE : feed back still active
After alarm reset ÜE still confirms alarm (only with VdS card).
Check ÜE device
HM:manually activated without fire
ÜE manually activated (only with VdS card).
check ÜE device
HM: no remote device feed back
ÜE activated but no confirmation (only with VdS card).
check wiring or ÜE device
HW/System error: Replace CPU board
Indicates a hardware problem.
unpower system and re−power again
(if message comes on again replace main board K3X...)
HW error: Mismatch board ######
HW warn.: Mismatch board ######
Actual configuration does not correspond with programmed
configuration.
check wiring and configuration
INCONSISTENT user data
Programmed user data and physical installation make do not
match.
start function ‘CHECK configuration’ via menu