line FAULT due to startup
Normal procedure during line startup. Duration: line reset =
50sec / line upload = 20sec or 40sec
no action to be taken
line ## > APMK too high: ###/###
Connection load on detector loop exceeded.
reduce the number of devices
line ## > config. INCOMPLETE
Line type defined but no devices configured.
configure line devices
line ## > TOO MANY devices (###)
Too many devices either more than 32 on a stub line or more
than 128 on a loop.
reduce the number of devices
line ## > WRONG or NO line type
Line type (stub’ or ‘loop’) wrong or not defined.
correct or define line type
line ##: invalid address −> ###
Illegal device address is polled either >128 (‘loop’) or >32
(‘stub’).
Acknowledge Reset 1)
line ## dev. ###−### NO RESPONSE
A range of devices is cut off due to line break(s) or short(s).
go to 1
st
or last cut off device and check wiring
line ## dev. REAL:## PROG:##
Difference between ‘seen’ and ‘programmed’ number of line
devices.
check planned and programmed line configuration
ln ##: BREAK / SHORT beh. dev ###
Break in detector loop at the displayed device address.
go to displayed device and check wiring
line ##: communication FAULT
Faulty communication on detector bus due to defective de-
vice(s), EMC−influences or too high line resistance.
devide detector loop into different parts then commission
one part after the other
line ##: SHORT CIRCUIT at dev. ###
Short circuit between the displayed device address and the
device before.
remove short circuit
ln ##, weak break seen at dev ###
Break or loose connection in the addressable line.
check the wiring at the indicated device
LON−interface card not detected
Configured RS232/LON card K3I080 not recognized
check connection
LON inconsistency in system
Installation and configuration on LON−bus do not match
check and update LON−bus configuration
LON device ## of unknown type
LON−bus device unknown by actual system software
replace or remove
LON type of address ## is wrong
Seen and configured type of LON−bus device do not match
check and change device type or configuration
LON device ## : no answer
No communication to configured LON−Bus device
check wiring also power supply
LON dev. ## is not parameterized
LON−bus device is set to address ‘0’
set device to valid address
LON dev. ## lost data
Local configuration data inside LON−bus device lost
check wiring and initiate SYSTEM−RESTART
LON inconsistency on addr.##
Type of LON−bus device does not match with config.
check device or correct LON−bus configuration
LON device inserted on addr ##
New LON−bus device added
check and update LON−bus configuration
mains POWER OFF
Mains voltage missing or fuse ’F9’/’F10’ blown (10min. delayed)
check internal fuses or external mains breakers
Missing telegram at LON dev. ##
Missing telegram at the LON device.
press ’Acknowledge’ than ’Reset’ on the operating panel
More than 16 LON devices found
More than 16 LON−devices connected
remove the devices that are too many