6.6 Control contacts
Pluggable terminal block K4/K14
FC330A / K3M010
Alarm contact 1 or 3
(active until reset)
1
2
3
4
NO
NC
C
NO
5
6
NC
C
Alarm contact 2 or 4
(active until reset)
max. 30V / 1A
Load
+
max. 30V / 1A
external system
CONTROL
Characteristics
Designed as dry changeover contacts
Active in alarm condition
Operating functions per control line (via menu)
ON/OFF switching
Activation (test)
Programmable functions per control line
Detector zone (alarm) from which ’alarm contact’ 1...4 is to be activated
Active on ’internal’ and ’external’ alarm or only on ’external’ alarm
Technical data
Contact rating max. 1A/30VDC