2.17 Connecting of collective SynoLINE600 devices (non current limited)
Note:for technical details see page 110
to run SynoLINE600 set jumper on the line extension card K3M010/020 accordingly see page 42, 43
list order and type of all devices (field device list)
+
++
AI340
micro terminals
AI300
−+−+−+
Response
indicator
AI340
max. 2 response indicators
L L
line
+
Smoke/heat detectors
L
L
DFB1190
Flame detector
1234
GH
GHQRVW
QRVW
Z
24VDC
as line coupler
EOL20
YXWVZMB
DLB1191A
DLO1191
DF1191/92
+
Linear smoke detector
Manual call points
line
+
EOL20
line
+
EOL20
(+)
(−)
SB3
4
3
2
1
Safety barrier
SB3
DC1192
−+−+−+
L L
−+−+−+
L L
or
EOL22Ex
Explosion hazard area
EOL22Ex
consult
local regulations
+ + + + +
–> set to ’collective’
(SynoLINE 600)
DC1192
−+−+−+
L L
−+−
−+−
−+
−+
* application also possible with CBA320A/DC1192
in ADDRESSABLE detector loop
−+
Resistor 1.2k or Z-Diode 5,6V
alarm
contact
EOL20
+
−+−+−+
L L
Signal contact
Intrinsically safe detectors
S terminate each detector line with
EOL20
S do not mix automatic detectors
with manual call points
S max. 32 smoke/heat detectors
per line DF1191/92 max. 5
DLO1191 max. 1
DM1103
Base SO620C
DO1101A-Ex
DT110xA-Ex
DM1103
Base SO620C
OP620C
Base SO620C Base SO620C
OH620C HI62xC
DM1103 DM1103
DM1103
++ +
line
+
EOL20
DM1101
DM1101 DM1101 DM1101
DM1103
DM1103