Fire Safety & Security Products
Building Technologies
1583_o_en_−−_6
108
08.2005
F
no
acknowledged
?
F
reset
?
yes
no
Confirm message
Investigate fire location and decide
Alarm stage 2
Local alarm
(alarm stage 1)
Remote alarm
Mode: ’manned’ ’unmanned’
’manned’
V1
V2
Reset
Ackn.
− emergency
− minor incident
Local alarm
or
’unmanned’
Local alarm (also called ’alarm stage 1’)
Alarm initiated by detectors during ’V1’ or ’V2’ is running
Remote alarm (also called ’alarm stage 2’)
Alarm initiating the remote transmission
− initiated in mode ’manned’ after ’V1’ or ’V2’ has expired
− immediately initiated by manual call point
− immediately initiated by any alarm during mode ’unmanned’
Alarm horn (acoustic alarm devices)
Activated either
− on ’remote alarm’ only or on ’local alarm’ + ’remote alarm’ default = remote alarm
− can be silenced via function key ’acknowledge’
The sound mode can be programmed either
− as ’continuous’ or ’pulsating’ signal default = pulsating
Special function ’EXTRA TIME’ Programming steps see page 74
Allows to set the system to ’manned’ after the automatic switchover has taken place for the preset time of
max. 9:00h
Zones excluded from alarm organization Programming steps see page 85
Zones that report ’non fire events’ can be excluded from the alarm organization
− Zones not initiating ’remote transmission’ (RT)
− Zones not initiating ’alarm horn’
or MULTI−LOC