122
08.2005
zone ### elem. ##: UNKNOWN state
Reported operating state does not correspond with device
type.
check and replace device
zone ### el. ##: WRONG application
Unsuitable application. Device has reported state ‘drift’ to often
within 24h.
replace device or change parameters
zone ### elem ##: FAULT
zone ### elem ##: SHORT
zone ### elem ##: BREAK
Fault at corresponding inputs on K3I110
check field wiring