5.8.1 Functions on level (4.4.1) 2. collective line
Functions as displayed Selectable options/Remarks
LINE ##: 1.DET 2.CP 3.BR=al 4.SH=al
> 5.CPsh=al 6.ALver 7.delay
.
1. autom. detector / break + short circuit = fault
2. Manual call point / break + short circuit = fault
3. Line break = alarm
4. Line short = alarm
5. Manual call point/ short circuit= alarm / break = fault
6. 1st alarm = Reset / 2nd alarm within 60 sec = alarm
7. Line break 1 min delayed
Multiple choices possible (exception: 2 with 5 or 7 not possible)
Note that with function 2/6/7 also function 1 is selected automatically,
same 4 with 5