EasyManua.ls Logo

Siemens Synova FC330A - Page 93

Siemens Synova FC330A
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fire Safety & Security Products
Building Technologies
1583_o_en_−−_5
89
08.2005
5.13.1 Linking procedure
Submenu 4. addressable line
to define line type, number of devices, link devices
to define device parameters
to define zone parameters
to define element parameters
to link conventional lines to zone (if available)
to check configuration before exit the programming mode
to delete all user data
to read actual line configuration as installed
to define control outputs
CONFIGURATION 1. line
(c) 2. device
3. zone
4. element
5. line ’collective’
6. CHECK configuration
7. CLEAR configuration
8. AUTOM. configuration
9. CONFIG ConTrol−ZONES
The linking of the conventional line to the logical ZONE is done automatically if during startup the function
’8.’ is selected. Therefore option ’5.’ is normally not needed.
The K3M010/020 always represent conventional lines 5...8 respectively 5....16
collective line ##
is LINKED to zone ###
(c.5) 1. LINK
2. UNLINK
collective line ##
is LINKED to zone ###
(c.5.1) LINK to (###−###)? ###
select the conventional line number with key ± or ° then
− enter ’1. ok
− select the ZONE number
− only ZONE in brackets can be selected
Advice:
− use the last ZONE numbers
select the conventional line number with key ± or ° then
− enter ’2. ok
− unlinked collective lines are not usable

Table of Contents

Other manuals for Siemens Synova FC330A

Related product manuals