08.2005
5.14.1 Define parameter on 9. CONFIG ConTrol−ZONES
Submenu 4. addressable line
to define line type, number of devices, link devices
to define device parameters
to define zone parameters
to define element parameters
to link conventional lines to zone (if available)
to check configuration before exit the programming mode
to delete all user data
to read actual line configuration as installed
to define control outputs
CONFIGURATION 1. line
(c) 2. device
3. zone
4. element
5. line ’collective’
6. CHECK configuration
7. CLEAR configuration
8. AUTOM. configuration
9. CONFIG ConTrol−ZONES
CONFIGURE: 1. ConTrol ZONES to define state active conTrol zone (trigger)
(c.9) 2. ConTrol ELEMENTS to define addressable output devices (AB....)
3. link DRIVER OUT’s to link driver outputs to conTrol zone
4. link RELAY OUT’s to link relay outputs to conTrol zone
2. add ConTrol zones
3. delete ConTrol zone
4. select ConTrol zone
5. configure
ConTrol zone ### has ## elements todefine related to zone or COMMON signal
1.TRIG cat:###### 2.ConTr zn:###### to define Normal control/Fire control 1)
3.TRIG crit.: ######, ############ to define WHEN the conTrol zone is activated
4.active UNTIL: ###### to define the DURATION of the active phase
Note:
1) There are additional operating facilities to
disable/enable for control zones with the attribute Fire:
– via input K6, via separate menu point (1.1)/(2.1) option ’4.’
DISABLE fire ctrl.
– via FBF key ’Steuerungen Aus’ (VdS card K3L070)
either
related to detector ZONE or
used as COMMON signal
Outputs
− driver outputs
− relay outputs
− DC outputs
conTrol zone related to
detector zone
detector
zone
conTrol
zone
trigger
trigger
conTrol zone not related to de-
tector zone but used as a
COMMON signal
Outputs
− driver outputs
− relay outputs
− DC outputs
conTrol
zone
Option ’3.’
Available functions:
a) if assigned to ZONE either
zone on ’alarm 1’ = ALARM 1
zone on ’alarm 2’ = ALARM 2
zone on ’fault’ = FAULT
zone ’disabled’ = DISABLED
zone on detector ’test’ = TEST
zone active ’technical’ = TECHZONE
zone on ’pre-alarm’ = PRE AL
functionality ’horn’ = AL HORN
functionality ’evac’ = EVAC
device on ’application warning’ = APPLwarn
device on ’drift’ = DRIFT
device on ’fault’ = DEV flt
zone on ’alarm 0’ = ALARM0
to remove all selected trigger = Erase...
(multiple choice possible max. 8)
Option ’4.’
to define the active phase either until occurence of
state ’inactive’ = state INACTIVE
command ’acknowledge’ = command ACK
b) if assigned to COMMON either
any zone on ’alarm 1’ = AL 1
any detector zone on ’alarm 2’ = AL2aut
any call point zone on ’alarm 2’ = AL2man
system ’fault’ = FAULT
system ’fault’ reversed = FLT inv
state ’isolation’ = ISOLAT
RT remote transm. ’disabled’ = RT DIS
any detector zone ’disabled’ = zn DIS
any zone on detector ’test’ = zn TEST
operating ’access’ provided = ACCESS
mode ’manned’ = MANNED
any other mode than NORMAL OPERATION = ANYMODE
pulse on ’ack’ =ACKPULSE
pulse on ’reset’ = RESPULSE
any ZONE automatic ’disabled’ = ANYAUTD
general ’fault’ (without zone fault) = FLT nozn
any zone on ’pre-alarm’ = PRE AL
> 1 detector zone on ’alarm’ = MULTI AL
functionality ’horn’ = AL HORN
functionality ’EVAC’ = EVAC
any detector on ’application warning’ = APPLwarn
any detector on ’drift’ = DRIFT
any device on ’fault’ = DEV flt
any zone on ’alarm 0’ = AL 0
alarm via input ’K6’ = AL K6
any ’FIRE control’ active = FIREctrl
mains ON = PWR ON
battery switching command = ACCUtest
to remove all selected trigger = Erase...
(multiple choice possible max. 8)
All control zones which are assigned as real ’fire controls’ can be disabled/enabled together
for testing purpose. Optical indicating controls, sounders etc. which are initiated via control
zones should not be assigned as fire controls.