EasyManua.ls Logo

Siemens Vector Control - Page 305

Siemens Vector Control
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
05.2006 Parameterizing Steps
Siemens AG 6SE7087-2JD60
SIMOVERT MASTERDRIVES Operating Instructions 9-13
Thermal motor
protection desired?
System with motor protection according to UL regulation?
The motor temperature is calculated via the motor current.
(In the pre-setting, motor overload protection in accordance with
UL regulation is activated!)
no yes
P382 = ?
P383 = ?
Specify motor cooling
0: self-ventilated
1: forced-ventilated
(automatically pre-set for P095 = 2, P097 > 0)
Enter the thermal time constant of the motor in s
The values can be taken from the table on the next page
(automatically pre-set for P095 = 2, P097 > 0).
The motor load limit (P384.2) is pre-assigned to 100 %.
P383 = 0
P095=2
P097>0
P700.01 = ?
Select setpoint and command source (sheet s0...s4, s6, s7)
0: PMU + MOP (Operation via the operator panel,
see next page for description)
1: Analog and digital inputs on the terminal strip
2: Fixed setpoints and digital inputs on the terminal strip
3: MOP and digital inputs on the terminal strip
4: USS1 (e.g. with SIMATIC)
5: not used
6: PROFIBUS (CBP)
7: OP1S and fixed setpoints via SCom1 (X300: PMU)
8: OP1S and MOP via SCom1 (X300: PMU)
P368 = ?
Enter the USS bus address
P740 = ?
P918.01 = ?
Enter the SIMOLINK module address
Enter the PROFIBUS address
P368 = 0,1,2,3 4,7 5 6
P370 = 1
Start of quick parameterization
0: No parameter change
1: Parameter change in acordance with selected combination
of parameter modules
(automatic factory setting according to P366)
(followed by automatic parameterization as for
P115 = 1)
P060 = 0
Return to the user menu
End of quick parameterization

Table of Contents

Related product manuals