05.2006 Control Word and Status Word
Siemens AG 6SE7087-2JD60
SIMOVERT MASTERDRIVES Operating Instructions 10-7
Bit 23: Restart-on-the-fly enable command (H "restart-on-the-fly enable")
HIGH signal
The command enables the restart-on-the-fly function.
Bit 24: Droop/technology controller enable command (H "droop/technology controller
enable")
HIGH signal
The command enables the droop function, if P100 (open-
loop/closed-loop control type) is assigned 3 (closed-loop frequency
control) or 4 (closed-loop speed control), parameter P246 <> 0 and
the inverted pulses of the drive converter are enabled.
The speed/frequency controller output, fed back as negative signal
to the speed/frequency setpoint, can be set via parameter P245
(source steady-state) and P246 (scaling steady-state)
Bit 25: Controller enable command (H "controller enable")
HIGH signal and the drive converter inverter pulses are enabled.
The speed controller output is enabled for the appropriate control
type (P100 = 0,4,5).
Bit 26: Command, external fault 2 (L "External fault 2")
LOW signal; it is only activated from the READY (011) condition
onwards and after an additional time delay of 200 ms.
FAULT (007) and fault message (F036).
The inverter pulses are inhibited, the main contactor, if available, is
opened.
Bit 27: Slave/master drive command (H "Slave drive")/(L "Master drive")
HIGH signal, P100 (open-loop/closed-loop control type) = 3, 4 (closed-
loop frequency/speed control), and the drive inverter pulses are
enabled.
Slave drive: The closed-loop control acts as closed-loop torque
control (M closed-loop control). With f closed-loop control, precise
torque control is not possible until from about 10 % of motor rated
speed onwards.
LOW signal, P100 (open-loop/closed-loop control type) = 3, 4 (closed-
loop frequency/speed control), and the drive converter inverter pulses
are enabled.
Master drive: The closed-loop control operates as closed-loop
speed or frequency control (closed-loop frequency/speed control).
Condition
Result
Condition
Result
Condition
Result
Condition
Result
Condition
Result
Condition
Result