Parameter description
AG05
Date: 15.06.2016 Art. No. 85677 Mod. status 139/16 Page 29 of 64
No.
Name
Selection
/ value
Default
Description
S
C
31
Type of
accelera-
tion
Inching
mode 2
0 - 1
0
Inching operation 2:
The type of acceleration can be set with this
parameter.
0 = static acceleration
Acceleration to final speed in one step as
defined under parameter no. 8.
1 = incremental acceleration
Acceleration to final speed as defined under
parameter no. 8 with the following
increments:
4 s to 20 % of final speed
2 s to 50 % of final speed
1 s to 100 % of final speed
S
1
32
Offset
-999999 to
999999
0
Offset value
Changes to the offset value are immediately
entered in the calculation of the position
value.
The following equation is applied in case of
calibration:
Position value = 0 + calibration value +
offset value
S
1
33
Baud rate
RS485
0 - 2
1
Baud rate of the RS485interface:
0 = 19200
1 = 57600
2 = 115200
Parameter changes become active only after
cold start or software reset.
S
5
34
Protocol
0 - 1
0
Protocol of the RS485 interface:
0 = SIKONETZ5
1 = Service protocol
Parameter changes become active only after
cold start or software reset.
S
5
35
Bus
Timeout
0 - 20
20
SIKONETZ5:
Notice! Unplanned device reactions.
Unplanned device reactions can occur with
time monitoring disabled ("0"= disabled)
and simultaneous cable break. In the
delivery state, time monitoring is enabled.
Mode: Time monitoring "disabled=0" is only
admissible for test purposes.
Enable time monitoring after leaving the
test mode.
1-20 = Bus Timeout values in x100 ms
Service protocol:
no function
S
4