41
Adv Earth Fault Diag Report
This report provides the following information for
Advanced Earth Fault Detection (AEFD):
Date and time of the test.
Address of the card that was tested.
Description of the card that was tested.
Circuit tested.
Type of test; All Circuits ON/OFF or a single circuit.
Quality of Ground Fault Isolation.
Measured impedance.
Polarity.
To generate a report, complete the following steps:
1. Press the MENU key. Use the NEXT and PREVIOUS keys to scroll through the choices until
the “PRINT REPORTS?” choice is displayed.
2. Use the NEXT and PREVIOUS keys to scroll through the categories of report (Alarm
History, Trouble History, etc.).
3. When the category of report you want to print is displayed, press ENTER. The system
prompts you to confirm that you want to generate the report. Press ENTER again.
The report prints on the panel’s report printer.
100BProcedure