EasyManua.ls Logo

Simplex 4100ES - Page 66

Simplex 4100ES
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
Example of an aborted (incompatible device problem) test
-----------------------------------------------------------------
Service Port Page 1
Report 6: TrueAlert Device Status Report 10:23:45am WED 07-FEB-07
TPS 3
SLC 1
POINT ID CUSTOM LABEL TEST RESULT
--------- --------------------------------- --------------------
3-1-1 Auditorium North PASSED
3-1-2 Auditorium South PASSED
3-1-3 Auditorium Lobby DEVICE NOT COMPATIBLE
NOMINAL CURRENT (A): 0.80
WORST_CASE CURRENT (A): 1.17
WORST_CASE VOLTAGE ABOVE/BELOW THRESHOLD (V): 1.2
SLC HAS NOT PASSED UNLESS ALL DEVICES ARE MARKED AS PASSED
-----------------------------------------------------------------
_______________________________________________________________________________
TrueNAC Voltage Drop Test, Continued
120BTrueNAC Report
Samples

Table of Contents

Other manuals for Simplex 4100ES

Related product manuals