EasyManuals Logo

Simplex 4100ES User Manual

Simplex 4100ES
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
81
Follow these steps to convert the Alert message playing on a group of speakers to an Evacuation
message.
1. On the EVAC display card, press the buttons corresponding to the floors currently playing the
Alert message (the LEDs on the Alert display card for these floors are lit).
2. Press the Selective Evac button.
When you do this, the following occurs.
The Alert message stops playing.
The Evacuation message starts playing.
The LEDs on the Alert Display Card turn off.
The LEDs on the EVAC display card that correspond to the buttons pressed in Step 1 turn on.
Note: If other floors were playing the Evacuation message, the evacuation message would start at the point it
is at on the other floors.
1. Press the All Speakers Talk button. The LED associated with this button illuminates, along
with the LEDs for each of the speaker circuits.
2. Key the microphone (depress the talk switch) and wait for the Ready to Talk LED to
illuminate. When this LED is ON, talk into the microphone. The page is routed to all speaker
circuits connected to the system.
1. Press the buttons corresponding to the floors requiring the page. The LEDs associated with
the selected buttons illuminate.
2. Key the microphone (depress the talk switch).
3. Wait for the Ready to Talk LED to illuminate and speak into the microphone to page the
floors selected in Step 1.
While a page is in progress, you can add floors to the existing page. To do this, follow these steps.
1. Press the buttons associated with the additional floors. The LEDs associated with these floors
turn ON and the page is heard on their speaker circuits
Continued on next page
Three to Eight Channel Audio System Operation, Continued
164BEvacuate Floors On
Which Alert
Message is Playing
165BPage Entire Building
166BPage Specific Floors
167BPage Additional
Floors

Table of Contents

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing

Related product manuals