Y070.020/GB Page 45
Operation instructions
SIPOS 5 PROFITRON, HiMod
6
Parameters and possible parameter values
6 Parameters and possible parameter values
Parameter
Default value
Parameter values
Explanation
For a detailed description, refer to chapters 5.4 and 5.5
cut-off mode op.
travel-dependent
travel-dependent
force-dependent
Cut-off mode in end position OPEN.
If the cut-off mode was changed, the end positions must (!) be set after-
wards.
cut-off force cl
50%
in 10 %-steps:
50 – 100 % F
max
Tripping force in kN in CLOSE direction.
cut-off force op
50%
in 10 %-steps:
50 – 100 % F
max
Tripping force in kN in OPEN direction.
Part-turn actuator 2SC5 or 2SG5
Act. time close
Up to 7 steps Positioning speed in CLOSE direction.
Parameterization within the positioning time range, refer to rating plate in 7
levels where each level is 1.4 times higher than the previous one.
Act. time open
Up to 7 steps Positioning time in OPEN direction.
Parameterization identical to positioning time in CLOSE direction.
Act. time em. cl
Up to 7 steps EMERGENCY positioning time in CLOSE direction.
Parameterization identical to positioning time in CLOSE direction.
Act. time em. op
Up to 7 steps EMERGENCY speed in OPEN direction.
Parameterization identical to positioning time in CLOSE direction.
cut-off mode cl.
travel-dependent
travel-dependent
torque-dependent
Cut-off mode in end position CLOSED.
If the cut-off mode was changed, the end positions must (!) be set after-
wards.
cut-off mode op.
travel-dependent
travel-dependent
torque-dependent
Cut-off mode in end position OPEN.
If the cut-off mode was changed, the end positions must (!) be set after-
wards.
max. cl. torque
30 %
50 %
in 10 % steps:
- standard (8 steps)
30 – 100 % Md
max
- modulating (6 steps)
50 – 100 % Md
max
Tripping torque in Nm in CLOSE direction.
For 2SG5… the tripping torque cannot be programmed.
max. op. torque
30 %
50 %
in 10 % steps:
- standard (8 steps)
30 – 100 % Md
max
- modulating (6 steps)
50 – 100 % Md
max
Tripping torque in Nm in OPEN direction.
For 2SG5… the tripping torque cannot be programmed.
Rotary actuator 2SA5, linear actuator 2SB5, part-turn actuator 2SC5 or 2SG5
retry torq.block
0
0 to 5 In case of block outside the end position range, the actuator repeatedly
moves against the block (1 to 5 times). Parameter value 0 means the posi-
tion does not have to be approached again.
rise time
0,5 s
in 0,1 s-steps
- Standard actuator:
0,1 bis 1,0 s
- Modulating actuator:
0,1 bis 2,0 s
The setting of the rise time infl uences the modulating behavior. Longer
rise times lead to higher modulating accuracy, which reduces the control
dynamics at the same time.
dc-brake
0%
0 - 250 %
in 1 % steps
A value not equal to „0 %“ triggers the DC brake via the integral frequency
converter. The higher the value, the higher the DC braking current is set.
For a value of „0 %“, the speed of the motor is reduced as quickly as
possible to a standstill via the frequency converter. For nearly all operation
points, this is the quickest way to achieve a standstill. We therefore recom-
mend maintaining the default settings.
mot. temp. warn.
135°C
0 - 155 °C
in 1°-steps
Warning after the motor temperature has reached the programmed value.
Parameterization not available for 2SG5.
mot. temp. prot.
On
On
Off
Disabling the motor protection will void the warranty for the motor.
motor heating
Off
On
Off
Depending on the motor temperature, the motor is heated at standstill with
DC current.
endpos. adjust
start with pos.
OPEN;
start with pos.
CLOSED
The mechanical end positions of the connected valve are adjusted to the
positioning range of the actuator, for the setting procedure refer to chapter
5.6.3, respectively 5.7.3 „Setting the end positions“.
rec.torque graph
rec.torque graph
curve no. 1, 2 or 3
Up to 3 torque reference curves can be recorded at different times. Diag-
nosis is enabled by means of comparison. Refer to chapter 7.4
„Recording the torque curves“.