6.2 Control system parameters
In the following the parameters and possible parameterizations for the process control are listed in a table. The following
example shows which information is included in which column.
Parameter
Default value
The parameters are
listed in this column.
The normal text marks
the default parame-
ters.
Explanation
This column contains explanations to the parameter on the left.
Parameter value
The possible parame-
ter values are listed
here.
This column contains explanations to the parameter value on the left.
Other param.
Here, you can proba-
bly nd other parame-
terizations.
This column contains explanations to the
parameterization on the left.
The presentation and the sequence of the parameters match the structure of the „commissioning“ menu and show the
parameters in the display. Use the
and buttons to scroll up and down between these parameters (refer to chapter
4.3.3, „Menu control – Navigation and changing of the parameters“).
Parameter
Default value
Explanation
Parameter value Other param.
endpos.range cl.
0% to 2%
From [0 % to 2 %]
to [0 % to 20 %]
in 1 % steps
Fig.: End position ranges
Within the end position range, travel is at a low speed (positioning speed or
long positioning time). If the actuator trips torque-dependently outside this
range, it is recognized as a fault („disabled in move“, refer to chapter 7.2).
endpos.range op.
98% to 100%
From [98 % to 100 %]
to [80 % to 100 %]
in 1 % steps
setpoint input
rising, 4-20mA
Setpoint for control
type „threshold
switch“ or „positioner“
option (is included
if either B, C, E, G,
H or K is entered at
position 15).
Setpoint at analog
input 1.
Fig.: Conversion of 0/4 – 20 mA into position setpoint 0 – 100 %
for different characteristics for positioner
setpoint slope
rising slope
rising: 20 mA corresponds to 100 % OPEN.
setpoint slope
falling slope
falling: 20 mA corresponds to 0 % OPEN.
setpoint range
4 mA – 20 mA
Detection of open-circuit behavior is possible
(live zero).
setpoint range
0 mA – 20 mA
Detection of open-circuit behavior is not possible
(dead zero).