Page 58 Y070.020/GB
7 Status and fault signals, diagnosis
7
Status and fault signals, diagnosis
7.2 Status and fault signals
No
Message Explanation Possible remedy
21
act. val. error
4
Fault at 0/4 – 20 mA output. Replace electronics.
31
blocked in move
2,3
A blockage of has been detected in the
travel. The actually required torque exceeds
the tripping torque,
oder
„Separate mount.“ parameter is set to
„>10m with lter“ although there is no LC-
lter available..
Check valve and torque setting, increase
tripping torque if necessary or use the
”Move again if blocked in move“ function!
Check MOV for sluggishness.
Check „Sep. mounting“ parameter.
Note: The actuator can still be moved elec-
trically in the opposite direction.
16
Bluetooth fault
A communication error is detected in the
Bluetooth module. The actuator still is ready
for operation and can be programmed using
the loal control station or COM-SIPOS via
the null modem cable.
Voltage OFF-ON. If the message is still
displayed, replace electronics unit
(Bluetooth board defective).
17
bus comm. fault
1
In eldbus communication, an interruption
has occurred (timeout). This error status is
only signaled as a fault, if the remote con-
trol is performed via eldbus.
Note: The bus address must deviate from
the default setting (126 for Pro bus and 247
for Modbus)!
Check bus communication and connection.
2
check end-pos.!
2
End position setting has not yet been
performed,
End position was passed due to hand-
wheel operation,
Friction coupling of the signaling gear
was twisted or the signal gear reduction
was changed or
Cut-off type was changed (e.g. from
torque-dependent to travel-dependent).
Perform end position adjustment once
again.
10
check parameters
2
No complete commissioning or
fault while saving commissioning data
caused by main-power fault.
Check settings and change, if required.
4
com. via bus
1
Commissioning via eldbus is active. In this
case, programming via the local control
station is not possible.
Wait for termination of commissioning via
bus.
18
DPR error
4
DualPortRAM fault. Replace electronics.
(Pro bus PCB defective.)
25
EEPROM error
4
EEPROM error. Replace electronics.
12
ElectrTmp fault
2,4
Electronics temperature cannot be determi-
ned, value of the electronics temperature is
set to 0 ° C.
Einstellungen prüfen und ggf. ändern.
19
ext.volt. fault
1
Mains failure/too low. Check power supply.
15
fault anal inp.
2,1
This message is only possible for
(4 – 20 mA) live-zero setting.
Threshold I: > 21 mA or < 3.6 mA.
check input current!
13
Fault I2C
2,4
No I2C communication possible. Voltage OFF-ON. If the message is still
displayed, replace electronics unit. (Control
board defective)
14
Fault I2C niP
2,4
No I2C communication possible. Voltage OFF-ON. If the message is still
displayed, replace electronics unit. (Control
board defective)
3
handwhl. pressed
1
Hand wheel/crank handle is pressed.
Cable to the hand wheel is defective.
Pull hand wheel and/or check cables/con-
tacts in the round plug.
Not for 2SG5…