Y070.020/GB Page 29
Operation instructions
SIPOS 5 PROFITRON, HiMod
5
Commissioning
5 Commissioning
Operation sequence
If the actuator is in the „commissioning“ menu, continue with operation step 2. For a detailed de-
scription of operation step 1, refer to chapter 5.3, „Access to the commissioning menu.“
1. Call up the main menu in the „locPar“ state, select
„commissioning“ menu and enter code 9044.
close direction
clockwise
2. Press
button, until “cut-off mode cl.” is indicated in the
display.
If the indicated parameter value is correct, continue
with operation step 6.
cut-off mode cl.
travel-dependent
3. Press the ENTER button to change the parameter
value. The selection is activated.
cut-off mode cl.
travel-dependent
4. Use the or button to change the parameter value.
The indication in the display differs depending on the
type of actuator:
– „torque-dependent“ for rotary and part-turn actuator,
– „travel -dependent“ for linear actuator.
cut-off mode cl.
torque-dependent
5. Press ENTER to save the change.
cut-off mode cl.
travel-dependent
6. Press the
button to change to the next parameter
“Cut-off mode op.” is displayed.
Repeat steps 3 to 5 to change the indicated parameter
value.
If the indicated parameter value is correct, continue
with point 7.
cut-off mode cl.
torque-dependent
7. Press the
button to change to the next parameter
The display shows the current value of the tripping
torque when closing.
Repeat steps 3 to 5 to change the indicated value.
If the indicated parameter value is correct, continue
with operation step 8.
max. cl. torque
18 Nm
8. Use the
button to change to the torque parameter for
the cut-off mode when opening.
Repeat steps 3 to 5 to change the indicated parameter
value.
max. op. torque
18 Nm
Now you can press the
button to get to the next parameter.
5.5 Other valve-specifi c parameters
The parameters described in this chapter have to be checked and changed, if necessary, during
commissioning. The operation sequence for changing the parameters is the same as described for
the previous parameters.
The parameters and possible parameter values are listed in a table in chapter 6.1 „Valve-specifi c
-specifi c parameters“.