Y070.020/GB Page 59
Operation instructions
SIPOS 5 PROFITRON, HiMod
7
Status and fault signals, diagnosis
7 Status and fault signals, diagnosis
No
Message Explanation Possible remedy
23
high curr. fault
3
Frequency converter has detected excessi-
ve current.
Check motor cable for short-circuit,
Check service conditions, e.g. ambient
temperature, exchange electronics, if
required.
28
high voltage
1
Mains voltage outside the tolerance +15 %.
Check connection voltage,
Check mains voltage for variations.
33
InitParams fault
4
The factory programming of the actuator is
missing or the EERPOM is defective.
Replace electronics.
Contact SIPOS service (service@sipos.de)!
24
inverter fault
1
Incorrect or no communication to the inver-
ter.
Check power supply,
otherwise contact SIPOS service (service@
sipos.de)!
29
inverter temp.
1
Temperature in the frequency converter too
high.
Check MOV for sluggishness,
Number of switching cycles too high,
Ambient temperature too high.
Firmware update if message occurs again.
9
local disabled
2
Status signal only!
Local control can be disabled via eldbus.
In case of a bus communication error local
control is automatically re-enabled.
Cancel change-over block via eldbus.
30
low voltage
1
Mains voltage outside the tolerance –10 %. Check power supply (voltage uctuations?)!
7
MotTemp too high
1
The motor has exceeded the maximum
temperature of 155 °C.
Possible reasons, e.g.:
Excessive ambient temperature,
Excessive run time (e.g. S2/ 15 min. has
been exceeded),
Too many switching cycles (e.g. 1,200
switching cycles have been exceeded),
Actually required torque too high,
- Short- circuited motor coil or
- Connection to the motor temperature
sensor interrupted (2SG5 only).
Parameter for separate mounting
„>10m with lter“ not set.
Note: The motor temperature monitoring can
be deactivated by programming at the ac-
tuator (PROFITRON only) (plant protection
has priority over motor protection). However,
the warranty for the actuator immediately
becomes void.
Check „Sep. mounting“ parameter.
11
moved too far
2
Position of the central wheel is too near to
the mechanical end stop of the signaling
gear.
The end positions have been exceeded
by hand wheel operation or
or the friction coupling in the signaling
gear was twisted or the signaling gear
ratio was changed.
End positon setting required
refer to chap-
ter 5.6 „Adjusting the signaling gear ratio
and the end positions“.
1
OpCirc BinInp
3
Error in checking the binary inputs (OPEN,
CLOSE, STOP, EMERGENCY):
The binary inputs have been parameterized
as “NC inputs” and low level (0V) is connec-
ted to all binary inputs.
Check parameterization of the binary inputs
and voltages at the binary inputs!
32
OpCirc PosInd
2,4
Cable to potentiometer or magnetic travel
sensor interrupted.
Check cables and contact points electro-
nics/gear,
Check cables for separate installation.
6
OpCirc TempInd
1
Connection to the temperature indicator
(PTC thermistor) interrupted.
Check cables/ contacts in the round plug.
8
Open circ. niP
2,4
No data is received by the non-intrusive
position encoder (niP).
Check cables and contact points electro-
nics/gear,
Check cables for separate installation.
26
RAM error
4
RAM error. Replace electronics.