Y070.020/GB Page 47
Operation instructions
SIPOS 5 PROFITRON, HiMod
6
Parameters and possible parameter values
6 Parameters and possible parameter values
Parameter
Default value
Explanation
Parameter value Other param.
binary inputs
NO
Control of the OPEN, CLOSE and STOP inputs.
NO Active for 24 V DC signal.
NC Active for 0 V DC signal.
emergency input
NO
Control of the EMERGENCY input.
NO Active for 24 V DC signal.
NC Active for 0 V DC signal.
remote control
PermCont BinInp
Depending on the version, the actuator can be controlled from the process control via different
control types (binary, analog or via fi eldbus).
PosCntr CurrInp Positioner with setpoint via analog setpoint input.
(The actuator moves the valve proportional to the analog signal 0/4 – 20
mA.) Only for enabled positioner.
PosCntr bus inp Positioner with setpoint via fi eldbus interface.
(The actuator operates the valve proportional to the digital signal.)
Only for available fi eldbus interface and enabled positioner.
tri-threshold Control via analog setpoint input:
0 – 30 % = CLOSE, 30 – 70 % = STOP, 70 – 100 % = OPEN
(The actuator moves if an analog signal is present within the OPEN or
CLOSE range, until the end position is reached or the signal changes to
the STOP range. A direct change of the direction of operation is possible).
PermCont BinInp Permanent contact via binary inputs with OPEN and CLOSE commands.
(The actuator moves as long as an OPEN or CLOSE signal is present.
The actuator stops, if the signal is deactivated, the end position has been
reached or the OPEN and CLOSE commands are present simultaneously.)
PermCont bus Permanent contact signal via PROFIBUS with OPEN and CLOSE
commands.
(The actuator moves as long as an OPEN or CLOSE signal is sent. The
actuator stops if the commands are deactivated in one of the following
telegrams or if the end position has been reached.)
Only for available fi eldbus interface.
PulsCont BinInp
Pulse contact signal via binary inputs (OPEN, CLOSE, STOP).
(After an OPEN/CLOSE pulse, the actuator operates until a STOP
command is present or the end position has been reached. A signal for the
opposite direction leads to a direct change of the direction of operation.)
Only possible if the „remote reconnect“ parameter is set to „non-active“.
two-wire-control Control via the binary input OPEN.
(The actuator moves if there is an active signal in OPEN direction, until the
end position has been reached. If the signal level is changed, the actuator
moves in CLOSE direction.)
proportion.conv The actuator is operated proportionally to the length of the pulse on the
OPEN/CLOSE binary inputs.
(The ratio of the actuator travel to the total travel is identical to the ratio of
duration of the operation pulse to the duration of the total positioning time.
Δ stroke
length of pulse
=
total stroke total stroke time
The entire positining time (run time) has to be parameterized to this end.
Refer to „proport.run time“ parameter.
Only for enabled positioner.
proportion. bus The actuator is operated proportionally to the length of the pulse via
fi eldbus.
Only for activated positioner function.