Table 10
71.10 - Table title - heading
Test frequency Band
a)
Service
a)
Modulation
b)
Maximum
power
Distance Immunity test level
MHz MHz W m V/m
385 380–390 TETRA 400
Puls modulation
b)
18 Hz
1,8 0,3 27
450
430–470
GMRS 460,
FRS 460
FM
c)
±5 kHz deviation
1 kHz sine
2
0,3
28
710
745
780
704–787
LTE band 13, 17
Pulsmodulation
b)
217 Hz
0,2
0,3
9
810
870
930
800–960
GSM 800/900,
TETRA 800,
IDEN 820,
CDMA 850,
LTE band 5
Puls modulation
b)
18 Hz
2
0,3
28
1 720
1 845
1 970
1 700–1 990
GSM 1800
CDMA 1900,
GSM 1900,
DECT
LTE band 1, 3, 4, 25; UMTS
Pulse modulation
b)
217 Hz
2
0,3
28
2 450
2 400–2 570
Bluetooth
WLAN
802.11 b/g/n
RFID 2450
LTE band 7
Pulse modulation
b)
217 Hz
2
0,3
28
5 240
5 500
5 785
5 100–5 800
WLAN 802.11 a/n
Pulse modulation
b)
217 Hz
0,2
0,3
9
NOTE: If necessary to achieve the immunity test level, the distance between the transmitting antenna and the ME equipment or
ME system may be reduced to 1 m. The 1 m test distance is permitted by IEC 61000-4-3.
a)
For some services, only the uplink frequencies are included.
b)
The carrier shall be modulated using a 50% duty cycle square wave signal.
c)
As an alternative to FM modulation, 50% pulse modulation at 18 Hz may be used because while it does not represent actual modulation, it would be worst case.