EasyManua.ls Logo

SKF Matrix Series - Page 23

SKF Matrix Series
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 10
71.10 - Table title - heading
Test frequency Band
a)
Service
a)
Modulation
b)
Maximum
power
Distance Immunity test level
MHz MHz W m V/m
385 380–390 TETRA 400
Puls modulation
b)
18 Hz
1,8 0,3 27
450
430–470
GMRS 460,
FRS 460
FM
c)
±5 kHz deviation
1 kHz sine
2
0,3
28
710
745
780
704–787
LTE band 13, 17
Pulsmodulation
b)
217 Hz
0,2
0,3
9
810
870
930
800–960
GSM 800/900,
TETRA 800,
IDEN 820,
CDMA 850,
LTE band 5
Puls modulation
b)
18 Hz
2
0,3
28
1 720
1 845
1 970
1 700–1 990
GSM 1800
CDMA 1900,
GSM 1900,
DECT
LTE band 1, 3, 4, 25; UMTS
Pulse modulation
b)
217 Hz
2
0,3
28
2 450
2 400–2 570
Bluetooth
WLAN
802.11 b/g/n
RFID 2450
LTE band 7
Pulse modulation
b)
217 Hz
2
0,3
28
5 240
5 500
5 785
5 100–5 800
WLAN 802.11 a/n
Pulse modulation
b)
217 Hz
0,2
0,3
9
NOTE: If necessary to achieve the immunity test level, the distance between the transmitting antenna and the ME equipment or
ME system may be reduced to 1 m. The 1 m test distance is permitted by IEC 61000-4-3.
a)
For some services, only the uplink frequencies are included.
b)
The carrier shall be modulated using a 50% duty cycle square wave signal.
c)
As an alternative to FM modulation, 50% pulse modulation at 18 Hz may be used because while it does not represent actual modulation, it would be worst case.
23

Table of Contents

Related product manuals